Dogu · Commercial
Dogu IGK heat recovery unit
Dogu IGK heat recovery unit. For offices, hotels and business centres. Speed is set with the switch supplied with the unit.


Commercial
Plate heat exchanger unit
IGK is Dogu's plate heat exchanger recovery unit, for offices, hotels and business centres. The stale outgoing air passes its heat to the incoming fresh air, with up to 50% recovery, and so lowers the energy needed for air conditioning.
It comes with AC or EC plug fans, quiet and efficient. The airflow is set with the switch supplied with the unit: 5 speeds with AC, 3 with EC. Nine sizes, from about 250 to 5,200 m³/h at 150 Pa external pressure.
- Airflow
- 250 to 5,200 m³/h
- Heat recovery
- up to 50%
- Fans
- AC or EC
Features
Up to 50% recovery
A cross-flow plate exchanger.
AC or EC
Quiet, efficient plug fans with high external static pressure.
Speed control
5 speeds with AC, 3 with EC, from the switch supplied with the unit.
G4 filter
Included as standard.
Room panel
LCD screen, weekly programming on the EC version, up to 50 m from the unit.
Options
Water coil or electric heater, duct silencer, temperature and CO₂ sensors.
Technical data
| Model | IGK-04 | IGK-07 | IGK-10 | IGK-15 | IGK-20 | IGK-30 | IGK-40 | IGK-50 | IGK-60 |
|---|---|---|---|---|---|---|---|---|---|
| Electrical supply | 1~ 230 V | 1~ 230 V | 1~ 230 V | 1~ 230 V | 1~ 230 V | 1~ 230 V | 1~ 230 V | 1~ 230 V | 3~ 380 V |
| With AC fans | |||||||||
| Airflow at 0 Pa, m³/h | 345 | 610 | 910 | 1125 | 1580 | 2350 | 3150 | 4155 | 5250 |
| Airflow at 150 Pa, m³/h | 255 | 495 | 800 | 985 | 1350 | 2000 | 2500 | 4140 | 5190 |
| Electrical power input, W | 128 | 270 | 414 | 424 | 634 | 1006 | 916 | 1388 | 2600 |
| Sound pressure at 1 m, dB(A) | 48 | 59 | 63 | 58 | 65 | 64 | 65 | 67 | 68 |
| With EC fans | |||||||||
| Airflow at 0 Pa, m³/h | 430 | 630 | 930 | 1160 | 1580 | 2700 | 3800 | 4400 | 5550 |
| Airflow at 150 Pa, m³/h | 380 | 540 | 805 | 1000 | 1510 | 2350 | 3400 | 4000 | 5100 |
| Electrical power input, W | 166 | 230 | 336 | 340 | 770 | 1000 | 1580 | 1500 | 2640 |
| Sound pressure at 1 m, dB(A) | 47 | 57 | 60 | 56 | 63 | 61 | 62 | 66 | 66 |
Product documentation
Specifications refer to the published series. We confirm the configuration, accessories and data for the proposed model in the quotation.
Selection and quotation
Comfort Clima helps identify the appropriate version and accessories for this product. Send us space usage, occupancy, required airflow and whether ductwork can be installed.
More in this category
Planning an order or project?
Send your equipment list, quantities and required date. We can help with selection and prepare a quotation for your requirements.
Contact
Tell us what you need
Whether you need one unit or equipment for an entire project, send your requirements with models, quantities and location. We will respond with a quotation and availability information.
- Call us
- +383 48 77 22 88
- Email us
- info@comfort-clima.com
- Find us
- Rruga Ukë Mavriqi 23, Shkabaj
Prishtina 10000, Kosovo - Hours
- Monday to Friday, 08:00–17:00
Your enquiry is ready to email
Complete the submission in your email application. If it did not open, call +383 48 77 22 88 or email info@comfort-clima.com.