Fujitsu · Outdoor unit · R32

Fujitsu AIRSTAGE J-V

Fujitsu AIRSTAGE J-V. A small, light unit with total piping up to 300 m. For offices and shops with many rooms.

Fujitsu AIRSTAGE J-VFujitsu

Outdoor unit · R32

Mini VRF

AIRSTAGE J-V is Fujitsu's R32 mini VRF with a single fan, more compact than the previous two-fan units. For offices and shops with many rooms.

Sizes 4, 5 and 6 HP (12.1 to 15.5 kW), single-phase 230 V or three-phase 400 V. It connects up to 14 indoor units, with up to 300 m of piping in total, and the shut-off valve comes as standard.

Cooling capacity
12.1 to 15.5 kW
Heating capacity
12.1 to 15.5 kW
Indoor units
up to 14

4 · 5 · 6 HP

Features

  • Small, light outdoor unit

    The single-fan chassis is more compact than the previous two-fan units, with more installation options.

  • Easy to install

    At under 1,008 mm tall, it fits narrow spots such as under windows or on roofs, without standing out.

  • Long piping

    Advanced refrigerant control allows up to 300 m of piping in total, for more freedom in system design.

  • Up to 14 indoor units

    Smaller indoor units and an optimised heat exchanger allow up to 14 indoor units.

  • Safety and easier installation

    The shut-off valve comes as standard. With the new indoor units with a built-in gas sensor, installation is much simpler.

  • Wide temperature range

    It works over a wider outdoor temperature range, for regions with different climates.

  • External static pressure

    Up to 35 Pa, so the outlet grille and duct can be fitted even when the unit is hidden in a small space.

  • Low-noise mode

    Five low-noise levels for fine control of the noise outside.

Technical data

ModelAJY040KBLAHAJY045KBLAHAJY054KBLAHAJY040KELAHAJY045KELAHAJY054KELAH
Capacity, HP456456
Electrical supply1~ 230 V1~ 230 V1~ 230 V3~ 400 V3~ 400 V3~ 400 V
Capacity and efficiency
Cooling capacity, kW12.114.015.512.114.015.5
Heating capacity, kW (in brackets: max.)12.1 (13.6)14.0 (16.0)15.5 (18.0)12.1 (13.6)14.0 (16.0)15.5 (18.0)
EER (cooling), W/W3.723.483.303.723.483.30
COP (heating), W/W4.524.684.454.524.684.45
SEER (cooling), W/W7.257.827.607.257.827.60
SCOP (heating, average climate), W/W4.504.734.714.504.734.71
Max. indoor units111214111214
Sound
Outdoor unit, dB(A)505252505252
Outdoor unit sound power, dB(A)687070687070
Dimensions and weight
Outdoor unit, mm (H × W × D)1008 × 1080 × 4801008 × 1080 × 4801008 × 1080 × 4801008 × 1080 × 4801008 × 1080 × 4801008 × 1080 × 480
Outdoor unit weight, kg117117117118118118
Installation and operation
Max. total pipe length, m300300300300300300
Max. height difference (outdoor unit above / below), m50 / 4050 / 4050 / 4050 / 4050 / 4050 / 40
Outdoor temperature range, cooling, °C−5 to 52−5 to 52−5 to 52−5 to 52−5 to 52−5 to 52
Outdoor temperature range, heating, °C−20 to 21−20 to 21−20 to 21−20 to 21−20 to 21−20 to 21
RefrigerantR32R32R32R32R32R32
Refrigerant charge, kg4.04.04.04.04.04.0

Product documentation

Specifications refer to the published series. We confirm the configuration, accessories and data for the proposed model in the quotation.

Selection and quotation

Comfort Clima helps identify the appropriate version and accessories for this product. Send us floor plans, room loads, unit locations, piping lengths and BMS requirements.

Planning an order or project?

Send your equipment list, quantities and required date. We can help with selection and prepare a quotation for your requirements.

Contact

Tell us what you need

Whether you need one unit or equipment for an entire project, send your requirements with models, quantities and location. We will respond with a quotation and availability information.

Find us
Rruga Ukë Mavriqi 23, Shkabaj
Prishtina 10000, Kosovo
Hours
Monday to Friday, 08:00–17:00

Your request

Your email application will open with a prepared enquiry. Select Send in that application to submit it.