Fujitsu · Outdoor unit · R410A

Fujitsu AIRSTAGE V-IV

Fujitsu AIRSTAGE V-IV. A large fan designed with CFD simulation, for powerful and quiet operation in large buildings.

Fujitsu AIRSTAGE V-IVFujitsu

Outdoor unit · R410A

For large buildings

AIRSTAGE V-IV is Fujitsu's R410A VRF for large buildings, with a large fan designed with CFD simulation, for powerful and quiet operation.

Single modules range from 8 to 16 HP (22.4 to 45 kW), three-phase 400 V; with 2 or 3 modules the system reaches 48 HP. Piping runs up to 700 m in total.

Cooling capacity
22.4 to 45.0 kW
Heating capacity
22.4 to 45.0 kW
Indoor units
up to 34

Features

  • Intelligent refrigerant control

    Control follows the room's heat load closely, for more comfort and energy saving.

  • Efficiency in real operation

    A proprietary heat exchanger and efficient DC twin rotary compressors give a high COP in every combination.

  • Large CFD-designed fan

    The CFD-designed fan gives high performance with quiet operation.

  • Efficiency technology

    A 3-phase DC fan motor, sine-wave DC inverter control, a 4-face heat exchanger and a subcooling heat exchanger.

  • Front air intake

    When several units stand together, the shaped front intake improves the airflow into the heat exchanger.

Technical data

ModelAJY072LALDHAJY090LALDHAJY108LALDHAJY126LALDHAJY144LALDH
Capacity, HP810121416
Electrical supply3N~ 400 V3N~ 400 V3N~ 400 V3N~ 400 V3N~ 400 V
Capacity and efficiency
Cooling capacity, kW22.428.033.540.045.0
Heating capacity, kW (in brackets: max.)22.4 (25.0)28.0 (31.5)33.5 (37.5)40.0 (45.0)45.0 (48.0)
EER (cooling), W/W3.763.093.513.032.68
COP (heating), W/W4.133.764.313.413.27
Max. indoor units1721263034
Sound
Outdoor unit, dB(A)5858586263
Outdoor unit sound power, dB(A)7979818486
Dimensions and weight
Outdoor unit, mm (H × W × D)1690 × 930 × 7651690 × 930 × 7651690 × 1240 × 7651690 × 1240 × 7651690 × 1240 × 765
Outdoor unit weight, kg252252275275275
Installation and operation
Max. total pipe length, m700700700700700
Max. height difference (outdoor unit above / below), m50 / 4050 / 4050 / 4050 / 4050 / 40
Outdoor temperature range, cooling, °C−15 to 46−15 to 46−15 to 46−15 to 46−15 to 46
Outdoor temperature range, heating, °C−20 to 21−20 to 21−20 to 21−20 to 21−20 to 21
RefrigerantR410AR410AR410AR410AR410A
Refrigerant charge, kg11.711.711.811.811.8

Product documentation

Specifications refer to the published series. We confirm the configuration, accessories and data for the proposed model in the quotation.

Selection and quotation

Comfort Clima helps identify the appropriate version and accessories for this product. Send us floor plans, room loads, unit locations, piping lengths and BMS requirements.

Planning an order or project?

Send your equipment list, quantities and required date. We can help with selection and prepare a quotation for your requirements.

Contact

Tell us what you need

Whether you need one unit or equipment for an entire project, send your requirements with models, quantities and location. We will respond with a quotation and availability information.

Find us
Rruga Ukë Mavriqi 23, Shkabaj
Prishtina 10000, Kosovo
Hours
Monday to Friday, 08:00–17:00

Your request