Haier · Indoor unit · Duct
Haier MRV compact duct 90 Pa
Haier MRV compact duct 90 Pa. 198 mm high, with up to 90 Pa for longer ducts. Fresh air inlet up to 20%.


Indoor unit · Duct
R32 / R410A
The 90 Pa compact duct is Haier's MRV indoor unit for bedrooms, hotel rooms and quiet spaces, where the duct is longer. It is only 198 mm high, installs horizontally or vertically, and works with R32 or in R410A systems.
Seven sizes from 1.3 to 5.6 kW cooling. The static pressure is selectable at 50 or 90 Pa, the condensate drain pump comes as standard, and there is a pre-cut fresh air inlet. Each size also comes in an external valve version (models ...D).
- Cooling capacity
- 1.3 to 5.6 kW
- Heating capacity
- 1.5 to 6.3 kW
- Airflow
- up to 990 m³/h
Features
Only 198 mm
Very slim, it fits even into low ceilings.
Horizontal or vertical installation
The unit can also be installed upright.
50 or 90 Pa static pressure
For longer ducts than the 40 Pa slim duct.
Condensate drain pump
Included as standard.
Bottom or rear air return
The air intake changes by moving the panel.
Fresh air
A pre-cut fresh air inlet.
7 fan speeds
DC inverter fan motor, with 7 speeds from the wired controller.
External valve (optional)
The ...D version has the electronic valve outside the unit.
Technical data
| Model | AD042MSFRAM | AD052MSFRAM | AD072MSFRAM | AD092MSFRAM | AD122MSFRAM | AD162MSFRAM | AD182MSFRAM |
|---|---|---|---|---|---|---|---|
| With external valve | AD042MSFRAD | AD052MSFRAD | AD072MSFRAD | AD092MSFRAD | AD122MSFRAD | AD162MSFRAD | AD182MSFRAD |
| Electrical supply | 1~ 220–240 V | 1~ 220–240 V | 1~ 220–240 V | 1~ 220–240 V | 1~ 220–240 V | 1~ 220–240 V | 1~ 220–240 V |
| Capacity and efficiency | |||||||
| Cooling capacity, kW | 1.3 | 1.5 | 2.2 | 2.8 | 3.6 | 4.5 | 5.6 |
| Heating capacity, kW | 1.5 | 1.8 | 2.5 | 3.2 | 4 | 5 | 6.3 |
| Airflow, m³/h (high / medium / low) | 385/280/210 | 385/280/210 | 495/360/270 | 528/384/288 | 660/480/360 | 820/600/450 | 990/720/540 |
| External static pressure, Pa | 50–90 | 50–90 | 50–90 | 50–90 | 50–90 | 50–90 | 50–90 |
| Sound | |||||||
| Indoor unit, dB(A) (high / medium / low) | 33/27/22 | 33/27/22 | 37/31/25 | 41/35/28 | 40/32/26 | 42/35/28 | 43/36/29 |
| Sound power, dB(A) (high / medium / low) | 50/42/39 | 50/44/39 | 54/48/42 | 58/52/45 | 57/49/43 | 59/52/45 | 60/53/46 |
| Dimensions and weight | |||||||
| Indoor unit, mm (W × D × H) | 700 × 450 × 198 | 700 × 450 × 198 | 700 × 450 × 198 | 700 × 450 × 198 | 900 × 450 × 198 | 1100 × 450 × 198 | 1100 × 450 × 198 |
| Weight, kg (standard / external valve) | 13.4 / 13.5 | 13.4 / 13.5 | 13.4 / 13.5 | 13.8 / 13.9 | 16.4 / 16.5 | 19.9 / 20 | 19.9 / 20 |
| Installation and operation | |||||||
| Pipes, liquid / gas, mm | 6.35 / 9.52 | 6.35 / 9.52 | 6.35 / 9.52 | 6.35 / 9.52 | 6.35 / 12.7 | 6.35 / 12.7 | 6.35 / 12.7 |
| Refrigerant | R32 / R410A | R32 / R410A | R32 / R410A | R32 / R410A | R32 / R410A | R32 / R410A | R32 / R410A |
Product documentation
Specifications refer to the published series. We confirm the configuration, accessories and data for the proposed model in the quotation.
Selection and quotation
Comfort Clima helps identify the appropriate version and accessories for this product. Send us floor plans, room loads, unit locations, piping lengths and BMS requirements.
More in this category
Planning an order or project?
Send your equipment list, quantities and required date. We can help with selection and prepare a quotation for your requirements.
Contact
Tell us what you need
Whether you need one unit or equipment for an entire project, send your requirements with models, quantities and location. We will respond with a quotation and availability information.
- Call us
- +383 48 77 22 88
- Email us
- info@comfort-clima.com
- Find us
- Rruga Ukë Mavriqi 23, Shkabaj
Prishtina 10000, Kosovo - Hours
- Monday to Friday, 08:00–17:00
Your enquiry is ready to email
Complete the submission in your email application. If it did not open, call +383 48 77 22 88 or email info@comfort-clima.com.